POLE QUANTITY | 2 |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 50.0 AMPERES AC ALL LOCATIONS |
CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
TERMINAL TYPE AND QUANTITY | 4 THREADED STUD |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC ALL LOCATIONS |
TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
RESET METHOD | MANUAL |
BODY STYLE | RECTANGULAR DIMENSIONAL ENVELOPE |
MOUNTING FACILITY TYPE AND QUANTITY | 4 THREADED HOLE |
CASE MATERIAL | PLASTIC |
TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC ALL LOCATIONS |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 7.000 MINIMUM AT 150 PCT AND |
| 31.000 MAXIMUM AT 150 PCT AND |
| 1.500 MINIMUM AT 300 PCT AND |
| 4.000 MAXIMUM AT 300 PCT AND |
| 0.600 MINIMUM AT 325 PCT AND |
| 2.000 MAXIMUM AT 325 PCT ALL LOCATIONS |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
OVERALL LENGTH | 3.330 INCHES NOMINAL |
OVERALL HEIGHT | 1.530 INCHES NOMINAL |
OVERALL WIDTH | 2.530 INCHES NOMINAL |
THREAD SERIES DESIGNATOR | UNC |
NOMINAL THREAD SIZE | 0.138 INCHES |
THREAD QUANTITY PER INCH | 32 |
MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
ACTUATOR FUNCTION | TRIP-RESET |
THE MANUFACTURERS DATA | |
MANUFACTURERS CODE | 16630 |
DESIGN CONTROL REFERENCE | 20A00-0057 |