| ACTUATOR FUNCTION | TRIP-RESET |
| ACTUATOR POSITION DESIGNATION | AT POLE ONE |
| CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
| INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | DUSTPROOF |
| INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SINGLE LOCATION |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| MATERIAL | PLASTIC CASE |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 80.0 AMPERES DC SINGLE LOCATION |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1500.0 DC SINGLE LOCATION |
| MOUNTING FACILITY TYPE AND QUANTITY | 2 THREADED HOLE(S) |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 30.0 DC SINGLE LOCATION |
| POLE QUANTITY | 1 |
| RESET METHOD | MANUAL |
| TERMINAL TYPE AND QUANTITY | 2 THREADED STUD |
| THREAD QUANTITY PER INCH | 32 |
| THREAD SERIES DESIGNATOR | UNIFIED NATIONAL COARSE (UNC) |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 40.000 NOMINAL AT 200 PCT AND 7.000 NOMINAL AT 300 PCT SINGLE LOCATION |
| TRIP RELEASE AMBIENT TEMP RATING | 25.0 CELSIUS MINIMUM SINGLE LOCATION |
| TRIP RELEASE CHARACTERISTIC | TIME DELAY SINGLE LOCATION |
| TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC SINGLE LOCATION |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 150.0 SINGLE LOCATION |