| ACTUATOR FUNCTION | TRIP-RESET |
| ACTUATOR POSITION DESIGNATION | AT EACH POLE |
| ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
| BODY STYLE | RECTANGULAR DIMENSIONAL ENVELOPE |
| CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE AND TWO LINKED |
| FRAGILITY FACTOR | MODERATELY RUGGED |
| FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
| INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | DUSTPROOF |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| MANUAL ACTUATOR TYPE AND QUANTITY | 2 TOGGLE |
| OVERALL HEIGHT | 1.500 INCHES NOMINAL |
| OVERALL LENGTH | 4.281 INCHES NOMINAL |
| OVERALL WIDTH | 1.875 INCHES NOMINAL |
| MATERIAL | PLASTIC CASE |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 40.0 AMPERES AC ALL LOCATIONS |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 600000.0 AC ALL LOCATIONS |
| MOUNTING FACILITY TYPE AND QUANTITY | 4 TERMINAL |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC ALL LOCATIONS |
| POLE QUANTITY | 2 |
| PRECIOUS MATERIAL AND LOCATION | CONTACT SURFACES SILVER |
| PRECIOUS MATERIAL | SILVER |
| RESET METHOD | MANUAL |
| SPECIAL HANDLING FEATURE | MAGNETIC |
| STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| TERMINAL TYPE AND QUANTITY | 2 SCREW AND 2 CLIP |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.150 MINIMUM AT 135 PCT AND 0.250 MINIMUM AT 180 PCT AND 0.800 MINIMUM AT 250 PCT ALL LOCATIONS |
| TRIP RELEASE AMBIENT TEMP RATING | 25.0 CELSIUS NOMINAL ALL LOCATIONS |
| TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
| TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 105.0 ALL LOCATIONS |