| ACTUATOR FUNCTION | TRIP-RESET |
| ACTUATOR POSITION DESIGNATION | AT POLE ONE |
| CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
| INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| MATERIAL | PLASTIC CASE |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 70.0 AMPERES AC ALL LOCATIONS |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 25000.0 AC ALL LOCATIONS |
| MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE(S) |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 600.0 AC ALL LOCATIONS |
| POLE QUANTITY | 3 |
| RESET METHOD | MANUAL |
| TERMINAL TYPE AND QUANTITY | 6 SCREW |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 6000.000 NOMINAL AT 125 PCT AND 500.000 NOMINAL AT 200 PCT AND 150.000 NOMINAL AT 300 PCT ALL LOCATIONS |
| TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
| TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |