| ACTUATOR FUNCTION | TRIP-RESET |
| ACTUATOR POSITION DESIGNATION | AT POLE TWO |
| BODY HEIGHT | 4.062 INCHES NOMINAL |
| BODY LENGTH | 10.000 INCHES NOMINAL |
| BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
| BODY WIDTH | 4.500 INCHES NOMINAL |
| BOSS HEIGHT | 0.250 INCHES NOMINAL |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.500 INCHES NOMINAL |
| CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| MATERIAL | PLASTIC CASE |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 75.0 AMPERES AC ALL LOCATIONS |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 15000.0 AC ALL LOCATIONS |
| MOUNTING FACILITY TYPE AND QUANTITY | 4 THREADED HOLE(S) |
| NOMINAL THREAD SIZE | 0.250 INCHES |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 500.0 AC ALL LOCATIONS |
| POLE QUANTITY | 3 |
| RESET METHOD | MANUAL |
| TERMINAL TYPE AND QUANTITY | 6 COMPRESSION |
| THREAD QUANTITY PER INCH | 20 |
| THREAD SERIES DESIGNATOR | UNIFIED NATIONAL COARSE (UNC) |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 3600.000 NOMINAL AT 150 PCT ALL LOCATIONS |
| TRIP RELEASE AMBIENT TEMP RATING | 50.0 CELSIUS NOMINAL ALL LOCATIONS |
| TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS AND TIME DELAY ALL LOCATIONS |
| TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 175.0 ALL LOCATIONS |