National Stock Number:
5925-00-411-0843

Federal Supply Class:
5925

National Item Identification Number:
004110843

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
3500053-00247WD8EVAC NORTH AMERICA INC
3500053-00258568ENVIROVAC INC DBA MONOGRAM SYSTEMS-ROCKFORD DIV
Q0U35014799SCHNEIDER ELECTRIC USA, INC.
F151561-351745AMERICAN DEVELOPMENT CORP
Q0U35056303SCHNEIDER ELECTRIC USA, INC.
802289-196214RAYTHEON COMPANY
QOU35056303SCHNEIDER ELECTRIC USA, INC.
Q0U35056365SCHNEIDER ELECTRIC USA, INC.


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE TWO
BODY HEIGHT2.360 INCHES MINIMUM AND 2.400 INCHES MAXIMUM
BODY LENGTH3.960 INCHES MINIMUM AND 4.000 INCHES MAXIMUM
BODY STYLEMULTIPOLE-SINGLE ACTUATOR TYPE
BODY WIDTH2.220 INCHES MINIMUM AND 2.270 INCHES MAXIMUM
BOSS HEIGHT0.220 INCHES MINIMUM AND 0.260 INCHES MAXIMUM
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH0.730 INCHES MINIMUM AND 0.770 INCHES MAXIMUM
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
FREQUENCY IN HERTZ60.0 ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
MATERIALPLASTIC CASE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE50.0 AMPERES AC ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS10000.0 AC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY6 UNTHREADED HOLE(S)
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS240.0 AC ALL LOCATIONS
POLE QUANTITY3
PRECIOUS MATERIAL AND LOCATIONCONTACTS SILVER
PRECIOUS MATERIALSILVER
RESET METHODMANUAL
UNTHREADED MOUNTING HOLE DIAMETER0.170 INCHES NOMINAL
TERMINAL TYPE AND QUANTITY6 COMPRESSION
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT0.008 MINIMUM AT 200 PCT AND 0.017 MAXIMUM AT 200 PCT ALL LOCATIONS
TRIP RELEASE AMBIENT TEMP RATING40.0 CELSIUS NOMINAL ALL LOCATIONS
TRIP RELEASE CHARACTERISTICTIME DELAY ALL LOCATIONS
TRIP RELEASE METHODTHERMAL-MAGNETIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 ALL LOCATIONS