| ACTUATOR FUNCTION | TRIP-RESET |
| BODY HEIGHT | 4.575 INCHES NOMINAL |
| BODY LENGTH | 5.000 INCHES NOMINAL |
| BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
| BODY WIDTH | 5.000 INCHES NOMINAL |
| BOSS HEIGHT | 0.312 INCHES NOMINAL |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 3.625 INCHES NOMINAL |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.688 INCHES NOMINAL |
| CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.500 INCHES NOMINAL |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 4.250 INCHES NOMINAL |
| FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| MATERIAL | PLASTIC CASE |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 100.0 AMPERES AC AND 100.0 AMPERES DC ALL LOCATIONS |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 10000.0 AC AND 5000.0 DC ALL LOCATIONS |
| MOUNTING FACILITY TYPE AND QUANTITY | 2 THREADED HOLE(S) |
| NOMINAL THREAD SIZE | 0.250 INCHES |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 125.0 AC AND 125.0 DC ALL LOCATIONS |
| POLE QUANTITY | 3 |
| RESET METHOD | MANUAL |
| TERMINAL TYPE AND QUANTITY | 6 QUICK DISCONNECT, FEMALE |
| THREAD QUANTITY PER INCH | 20 |
| THREAD SERIES DESIGNATOR | UNIFIED NATIONAL COARSE (UNC) |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 10.000 MINIMUM AT 200 PCT AND 210.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
| TRIP RELEASE AMBIENT TEMP RATING | 50.0 CELSIUS NOMINAL ALL LOCATIONS |
| TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS AND TIME DELAY ALL LOCATIONS |
| TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 115.0 ALL LOCATIONS |