| CUBIC MEASURE | 55.314 CUBIC INCHES |
| FRAGILITY FACTOR | MODERATELY RUGGED |
| 12.000 MAXIMUM AT 500 PCT AND |
| 0.440 MINIMUM AT 1000 PCT AND |
| 2.400 MAXIMUM AT 1000 PCT AND |
| 0.590 NOMINAL AT 2000 PCT ALL LOCATIONS |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| BODY LENGTH | 6.312 INCHES NOMINAL |
| BODY WIDTH | 2.750 INCHES NOMINAL |
| BODY HEIGHT | 3.140 INCHES NOMINAL |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 4.620 INCHES NOMINAL |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.380 INCHES NOMINAL |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 4.620 INCHES NOMINAL |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.375 INCHES NOMINAL |
| BOSS HEIGHT | 0.710 INCHES NOMINAL |
| MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| ACTUATOR FUNCTION | TRIP-RESET |
| ACTUATOR POSITION DESIGNATION | AT POLE TWO |
| ARC QUENCHING METHOD | AIR |
| STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| POLE QUANTITY | 2 |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 40.0 AMPERES AC AND |
| 40.0 AMPERES DC ALL LOCATIONS |
| CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| TERMINAL TYPE AND QUANTITY | 4 SCREW |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 480.0 AC AND |
| 250.0 DC ALL LOCATIONS |
| TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS AND |
| 9.000 MINIMUM AT 300 PCT AND |
| 37.500 MAXIMUM AT 300 PCT AND |
| 4.250 MINIMUM AT 400 PCT AND |
| 18.000 MAXIMUM AT 400 PCT AND |
| 2.400 MINIMUM AT 500 PCT AND |
| TIME DELAY ALL LOCATIONS |
| RESET METHOD | MANUAL |
| BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
| MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE |
| CASE MATERIAL | PLASTIC |
| TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
| FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 18000.0 AC AND |
| 10000.0 DC ALL LOCATIONS |
| TRIP RELEASE AMBIENT TEMP RATING | 10.0 DEG CELSIUS MINIMUM AND |
| 50.0 DEG CELSIUS MAXIMUM ALL LOCATIONS |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 725.000 MINIMUM AT 100 PCT AND |
| 1000.000 MAXIMUM AT 100 PCT AND |
| 30.000 MINIMUM AT 200 PCT AND |
| 125.000 MAXIMUM AT 200 PCT AND |
| 15.000 MINIMUM AT 250 PCT AND |
| 60.000 MAXIMUM AT 250 PCT AND |