| ACTUATOR FUNCTION | TRIP-RESETTRIP-RESET |
| ACTUATOR POSITION DESIGNATION | AT POLE TWOAT POLE TWO |
| BODY HEIGHT | 4.094 INCHES NOMINAL4.094 INCHES NOMINAL |
| BODY LENGTH | 6.500 INCHES NOMINAL6.500 INCHES NOMINAL |
| BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPEMULTIPOLE-SINGLE ACTUATOR TYPE |
| BODY WIDTH | 4.125 INCHES NOMINAL4.125 INCHES NOMINAL |
| BOSS HEIGHT | 0.188 INCHES NOMINAL0.188 INCHES NOMINAL |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 3.938 INCHES NOMINAL3.938 INCHES NOMINAL |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.375 INCHES NOMINAL1.375 INCHES NOMINAL |
| CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONSOVERCURRENT ALL LOCATIONS |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 2.750 INCHES NOMINAL2.750 INCHES NOMINAL |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.625 INCHES NOMINAL2.625 INCHES NOMINAL |
| FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS60.0 ALL LOCATIONS |
| INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANTFUNGUS RESISTANT |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREETRIP FREE |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 500.0 AC AND 500.0 AC AND 250.0 DC ALL LOCATIONS250.0 DC ALL LOCATIONS |
| MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE1 TOGGLE |
| MATERIAL | PLASTIC CASEPLASTIC CASE |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 25.0 AMPERES AC AND 25.0 AMPERES AC AND 25.0 AMPERES DC ALL LOCATIONS25.0 AMPERES DC ALL LOCATIONS |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 15000.0 AC AND 15000.0 AC AND 10000.0 DC ALL LOCATIONS10000.0 DC ALL LOCATIONS |
| MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE(S)4 UNTHREADED HOLE(S) |
| POLE QUANTITY | 33 |
| RESET METHOD | MANUALMANUAL |
| TRIP RELEASE AMBIENT TEMP RATING | 50.0 CELSIUS NOMINAL ALL LOCATIONS50.0 CELSIUS NOMINAL ALL LOCATIONS |
| TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS ALL LOCATIONSINSTANTANEOUS ALL LOCATIONS |
| TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONSTHERMAL-MAGNETIC ALL LOCATIONS |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 138.0 ALL LOCATIONS138.0 ALL LOCATIONS |
| UNTHREADED MOUNTING HOLE DIAMETER | 0.281 INCHES NOMINAL0.281 INCHES NOMINAL |
| TERMINAL TYPE AND QUANTITY | 6 THREADED STUD6 THREADED STUD |