5925-01-070-4829 CIRCUIT BREAKER Index 5925-01-070-4831 CIRCUIT BREAKER

National Stock Number:
5925-01-070-4830

Federal Supply Class:
5925

National Item Identification Number:
010704830

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
JA1-B2-3-374193EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV
JA1-B2-A-3-34K035AIRPAX ELECTRONICS DIV OF NORTH AMERICAN PHILLIP CO INC
JA1-B2A-3-30CBB3WESTINGHOUSE ELECTRIC CORP DEFENSE AND ELECTRONICS CENTER MS 6225
JA1-B2A-3-36A604TERRAQUIP INCORPORATED
JA1-B2A-3-381118EATON CORPORATION
JA1-B2A-3-39A329SOUTHERN ELECTRIC SUPPLY CO DBA REXEL INC. DIV REXEL DAYTON


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE ONE
ARC QUENCHING METHODMAGNETIC BLOWOUT
BODY LENGTH1.985 INCHES MINIMUM AND 2.015 INCHES MAXIMUM
BODY STYLESINGLE POLE TYPE
BODY WIDTH0.745 INCHES MINIMUM AND 0.755 INCHES MAXIMUM
BOSS HEIGHT0.125 INCHES MINIMUM AND 0.135 INCHES MAXIMUM
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH1.555 INCHES MINIMUM AND 1.565 INCHES MAXIMUM
CIRCUIT PROTECTION TYPEOVERCURRENT SINGLE LOCATION
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH1.655 INCHES MINIMUM AND 1.665 INCHES MAXIMUM
FRAGILITY FACTORMODERATELY RUGGED
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDDUSTPROOF AND FUNGUS PROOF
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP SINGLE LOCATION
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
MATERIALPLASTIC CASE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE3.0 AMPERES DC SINGLE LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS1000.0 DC SINGLE LOCATION
MOUNTING FACILITY TYPE AND QUANTITY2 THREADED HOLE
MOUNTING SURFACE TO TERMINAL END DISTANCE1.875 INCHES MINIMUM AND 1.885 INCHES MAXIMUM
NOMINAL THREAD SIZE0.138 INCHES
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS65.0 DC SINGLE LOCATION
POLE QUANTITY1
PRECIOUS MATERIAL AND LOCATIONCONTACTS SILVER
PRECIOUS MATERIALSILVER
RESET METHODMANUAL
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
TERMINAL TYPE AND QUANTITY2 TAB, SOLDER LUG
THREAD QUANTITY PER INCH32
THREAD SERIES DESIGNATORUNC
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT0.800 MINIMUM AT 200 PCT AND 1.800 MAXIMUM AT 200 PCT SINGLE LOCATION
TRIP RELEASE CHARACTERISTICTIME DELAY SINGLE LOCATION
TRIP RELEASE METHODMAGNETIC-HYDRAULIC SINGLE LOCATION
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 SINGLE LOCATION