5925-01-085-1214 CIRCUIT BREAKER Index 5925-01-085-1216 CIRCUIT BREAKER

National Stock Number:
5925-01-085-1215

Federal Supply Class:
5925

National Item Identification Number:
010851215

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
4330-001-0050076374SAFRAN ELECTRICAL & POWER USA, LLC
4330-001-576374SAFRAN ELECTRICAL & POWER USA, LLC
AS141540U583SAE INTERNATIONAL
92057934228L3 TECHNOLOGIES, INC.
AS1415481343SOCIETY OF AUTOMOTIVE ENGINEERS INC
5925PL19964679009HINSPEKTORAT WSPARCIA SIL ZBROJNYCH
AS580910U583SAE INTERNATIONAL
MS14154-50U583SAE INTERNATIONAL
MS14154-581343SOCIETY OF AUTOMOTIVE ENGINEERS INC
AS5809181343SOCIETY OF AUTOMOTIVE ENGINEERS INC
MIL-C-580981349MILITARY SPECIFICATIONS PROMULGATED BY MILITARY DEPARTMENTS/AGENCIES UNDER AUTHORITY OF DEFENSE STANDARDIZATION MANUAL 4120 3-M
MS14154-0596906MILITARY STANDARDS PROMULGATED BY MILITARY DEPARTMENTS UNDER AUTHORITY OF DEFENSE STANDARDIZATION MANUAL 4120 3-M
MS14154-596906MILITARY STANDARDS PROMULGATED BY MILITARY DEPARTMENTS UNDER AUTHORITY OF DEFENSE STANDARDIZATION MANUAL 4120 3-M
LS10159-5P98897LOCKHEED MARTIN CORP
SAE-AS580910U583SAE INTERNATIONAL
SAE AS1415481343SOCIETY OF AUTOMOTIVE ENGINEERS INC
MS14154-5A0126LEONARDO SPA HELICOPTERS DIVISION -PRODUCTION SITE


Techincal Specification:
POLE QUANTITY3
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE5.0 AMPERES AC ALL LOCATIONS
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
TERMINAL TYPE AND QUANTITY6 SCREW
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS200.0 AC ALL LOCATIONS
TRIP RELEASE CHARACTERISTICTIME DELAY ALL LOCATIONS
RESET METHODMANUAL
BODY STYLEMULTIPOLE-SINGLE ACTUATOR TYPE
MOUNTING FACILITY TYPE AND QUANTITY1 THREADED BUSHING
CASE MATERIALPLASTIC
TRIP RELEASE METHODTHERMAL ALL LOCATIONS
FREQUENCY IN HERTZ400.0 ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS5000.0 AC ALL LOCATIONS
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP ALL LOCATIONS
TRIP RELEASE AMBIENT TEMP RATING25.0 DEG CELSIUS NOMINAL ALL LOCATIONS
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT4.000 MINIMUM AT 200 PCT AND
20.000 MAXIMUM AT 200 PCT ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT135.0 ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
BUSHING LENGTH0.219 INCHES MINIMUM AND
0.281 INCHES MAXIMUM
BODY LENGTH0.781 INCHES MAXIMUM
BODY WIDTH1.840 INCHES MAXIMUM
BODY HEIGHT1.381 INCHES MAXIMUM
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH0.469 INCHES MINIMUM AND
0.531 INCHES MAXIMUM
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH0.593 INCHES MINIMUM AND
0.655 INCHES MAXIMUM
THREAD SERIES DESIGNATORUNS
NOMINAL THREAD SIZE0.469 INCHES
THREAD QUANTITY PER INCH32
MANUAL ACTUATOR TYPE AND QUANTITY1 PUSH-PULL
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE TWO
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS PROOF AND
SHOCKPROOF AND
VIBRATIONPROOF
TEST DATA DOCUMENT81349-MIL-C-5809 SPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS, BROCHURES,ETC., THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS, INDUSTRY DIRECTORIES, AND SIMILAR TRADE PUBLICATIONS, REFLECTING GENERAL TYPE DATA ON CERTAIN ENVIRONMENTAL AND PERFORMANCE REQUIREMENTS AND TEST CONDITIONS THAT ARE SHOWN AS "TYPICAL", "AVERAGE", "NOMINAL", ETC.).
ARC QUENCHING METHODMAGNETIC BLOWOUT
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
FRAGILITY FACTORMODERATELY RUGGED
SPECIFICATION/STANDARD DATA96906-MS14154-5 GOVERNMENT STANDARD


Click here to Register for Free 30-day Trial