5975-01-086-5640 CONDUIT,METAL,FLEXIBLE Index 5925-01-086-5642 CIRCUIT BREAKER

National Stock Number:
5925-01-086-5641

Federal Supply Class:
5925

National Item Identification Number:
010865641

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
6TC2-582647SENSATA TECHNOLOGIES, INC.
6TC2-5B82647SENSATA TECHNOLOGIES, INC.


Techincal Specification:
POLE QUANTITY3
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE5.0 AMPERES AC ALL LOCATIONS
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
TERMINAL TYPE AND QUANTITY6 SCREW
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS120.0 AC ALL LOCATIONS
TRIP RELEASE CHARACTERISTICTIME DELAY ALL LOCATIONS
RESET METHODMANUAL
BODY STYLEMULTIPOLE-SINGLE ACTUATOR TYPE
MOUNTING FACILITY TYPE AND QUANTITY1 THREADED BUSHING
CASE MATERIALPLASTIC
TRIP RELEASE METHODTHERMAL ALL LOCATIONS
FREQUENCY IN HERTZ400.0 ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS2000.0 AC ALL LOCATIONS
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP ALL LOCATIONS
TRIP RELEASE AMBIENT TEMP RATING25.0 DEG CELSIUS MAXIMUM ALL LOCATIONS
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT4.000 MINIMUM AT 200 PCT AND
20.000 MAXIMUM AT 200 PCT AND
0.400 MINIMUM AT 500 PCT AND
2.000 MAXIMUM AT 500 PCT AND
0.100 MINIMUM AT 1000 PCT AND
0.530 MAXIMUM AT 1000 PCT ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT145.0 ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
BUSHING LENGTH0.219 INCHES MINIMUM AND
0.281 INCHES MAXIMUM
BODY LENGTH1.840 INCHES MAXIMUM
BODY WIDTH0.730 INCHES MINIMUM AND
0.770 INCHES MAXIMUM
BODY HEIGHT1.319 INCHES MINIMUM AND
1.381 INCHES MAXIMUM
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH0.469 INCHES MINIMUM AND
0.531 INCHES MAXIMUM
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH0.593 INCHES MINIMUM AND
0.655 INCHES MAXIMUM
THREAD SERIES DESIGNATORUNS
NOMINAL THREAD SIZE0.438 INCHES
THREAD QUANTITY PER INCH32
MANUAL ACTUATOR TYPE AND QUANTITY1 PUSH-PULL
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE TWO
EXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE, TWO, AND THREE LINKED


Click here to Register for Free 30-day Trial