5925-01-397-4948 CIRCUIT BREAKER Index 7340-01-397-4950 SPOON,TEA

National Stock Number:
5925-01-397-4949

Federal Supply Class:
5925

National Item Identification Number:
013974949

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
ED23B04066842SIEMENS ENERGY AND AUTOMATION INC ITE CIRCUIT PROTECTION DIV


Techincal Specification:
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
FREQUENCY IN HERTZ60.0 ALL LOCATIONS
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MATERIALPLASTIC CASE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE40.0 AMPERES AC ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS15000.0 AC ALL LOCATIONS
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS240.0 AC ALL LOCATIONS
POLE QUANTITY3
RESET METHODMANUAL
TRIP RELEASE CHARACTERISTICINSTANTANEOUS ALL LOCATIONS
TRIP RELEASE METHODMAGNETIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 ALL LOCATIONS