| AUXILIARY TRIP COIL VOLTAGE TYPE AND RATING IN VOLTS | 220.0 AC NOMINAL ALL LOCATIONS |
| BODY LENGTH | 6.000 INCHES NOMINAL |
| BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
| BODY WIDTH | 4.125 INCHES NOMINAL |
| BOSS HEIGHT | 0.250 INCHES NOMINAL |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 5.000 INCHES NOMINAL |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.375 INCHES NOMINAL |
| CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.375 INCHES NOMINAL |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 4.687 INCHES NOMINAL |
| FREQUENCY IN HERTZ | 50.0 OR 60.0 ALL LOCATIONS |
| INTERNAL TRIP RELEASE CONFIGURATION | SERIES/RELAY TRIP ALL LOCATIONS |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| MATERIAL | PLASTIC CASE |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 3.0 AMPERES AC ALL LOCATIONS |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 5000.0 AC ALL LOCATIONS |
| MOUNTING FACILITY TYPE AND QUANTITY | 4 SLOT |
| MOUNTING SURFACE TO TERMINAL END DISTANCE | 3.125 INCHES NOMINAL |
| MOUNTING SLOT WIDTH | 0.203 INCHES NOMINAL |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 480.0 AC ALL LOCATIONS |
| SPECIAL FEATURES | 2 ELECTRICALLY ISOLATED COILS; COIL NUMBER 1 TIME DELAY; COIL NUMBER 2 INSTANTANEOUSLY TRIPPED BY CURRENT(220.0 VOLTS, 50.0 TO 60.0 HERTZ, 30.0 VA), SUPPLIED BY CONTROL EQUIPMENT OR REMOTE MONITORING SYSTEM; ULTIMATE TRIP RATING FOR COIL 2 IS 120.0 PERCENT |
| POLE QUANTITY | 3 |
| RESET METHOD | MANUAL |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.150 MINIMUM AT 200 PCT AND 0.600 MAXIMUM AT 200 PCT ALL LOCATIONS |
| TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS AND TIME DELAY ALL LOCATIONS |
| TRIP RELEASE DUTY CYCLE | INTERMITTENT ALL LOCATIONS |
| TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |