4010-00-080-9818 CHAIN ASSEMBLY,SINGLE LEG Index 3950-00-080-9822 HOIST,CHAIN

National Stock Number:
6145-00-080-9821

Federal Supply Class:
6145

National Item Identification Number:
000809821

Description:
CABLE,POWER,ELECTRICAL

Detail:
Two or more insulated conductors (solid or stranded) contained in a common covering, or two or more insulated conductors twisted or molded together without a common covering, or one insulated conductor with a metallic covering, covering, shield, or outer conductor. The rated working voltage of the item must be 300 volts or more, or in lieu of this the test voltage must be 1,000 volts or more; and the size of each individual conductor must be number 18 American Wire Gage (0.75 SQUARE MILLIMETERS) or larger. For cables with uninsulated neutral conductor use the hightest rated voltage. Refers to bulk quantities only, for items of definite length with processed ends or terminated in fittings, see CABLE ASSEMBLY, POWER, ELECTRICAL. For low voltage aircraft and automotive cable, see CABLE, SPECIAL PURPOSE, ELECTRICAL.


Manufacturer Information:
C0-03MDF(3/12)050281349MILITARY SPECIFICATIONS PROMULGATED BY MILITARY DEPARTMENTS/AGENCIES UNDER AUTHORITY OF DEFENSE STANDARDIZATION MANUAL 4120 3-M
CO-03MDF(3/12)050281349MILITARY SPECIFICATIONS PROMULGATED BY MILITARY DEPARTMENTS/AGENCIES UNDER AUTHORITY OF DEFENSE STANDARDIZATION MANUAL 4120 3-M
M3432-03MDF 3/12 050281349MILITARY SPECIFICATIONS PROMULGATED BY MILITARY DEPARTMENTS/AGENCIES UNDER AUTHORITY OF DEFENSE STANDARDIZATION MANUAL 4120 3-M
M3432-03MDF(3/12)050281349MILITARY SPECIFICATIONS PROMULGATED BY MILITARY DEPARTMENTS/AGENCIES UNDER AUTHORITY OF DEFENSE STANDARDIZATION MANUAL 4120 3-M
M3432-03MDF(3/12)50281349MILITARY SPECIFICATIONS PROMULGATED BY MILITARY DEPARTMENTS/AGENCIES UNDER AUTHORITY OF DEFENSE STANDARDIZATION MANUAL 4120 3-M
MIL-C-343281349MILITARY SPECIFICATIONS PROMULGATED BY MILITARY DEPARTMENTS/AGENCIES UNDER AUTHORITY OF DEFENSE STANDARDIZATION MANUAL 4120 3-M
MIL-DTL-343281349MILITARY SPECIFICATIONS PROMULGATED BY MILITARY DEPARTMENTS/AGENCIES UNDER AUTHORITY OF DEFENSE STANDARDIZATION MANUAL 4120 3-M


Techincal Specification:
TEST DATA DOCUMENTMIL-DTL-3432 SPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS, BROCHURES,ETC., THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS, INDUSTRY DIRECTORIES, AND SIMILAR TRADE PUBLICATIONS, REFLECTING GENERAL TYPE DATA ON CERTAIN ENVIRONMENTAL AND PERFORMANCE REQUIREMENTS AND TEST CONDITIONS THAT ARE SHOWN AS "TYPICAL", "AVERAGE", "NOMINAL", ETC.).
SPECIFICATION/STANDARD DATA81349-MIL-DTL-3432 GOVERNMENT SPECIFICATION
SPEC/STD CONTROLLING DATA
NON-DEFINITIVE GOVERNMENT SPEC/STD REFERENCEMIL-DTL-3432
MANUFACTURERS CODE81349
DEFINITIVE GOVERNMENT SPEC/STD REFERENCEM3432-03MDF(3/12)0502
CONDUCTOR QUANTITY3
CONDUCTOR FORMSTRANDED ALL CONDUCTORS
MATERIALCOPPER CORE CONDUCTOR ALL CONDUCTORS
RUBBER BUTADIENE-STYRENE CLASS SBR 1ST POSITION PRIMARY INSULATION ALL CONDUCTORS
RUBBER CHLOROPRENE CLASS CR 1ST POSITION JACKET CABLE
MATERIAL DOCUMENT AND CLASSIFICATIONQQ-W-343,SOFT FED SPEC SINGLE MATERIAL RESPONSE CORE CONDUCTOR ALL CONDUCTORS
MIL-I-3930,TYPE IS-L MIL SPEC SINGLE MATERIAL RESPONSE 1ST POSITION PRIMARY INSULATION ALL CONDUCTORS
MIL-I-3930,TYPE JN-L MIL SPEC SINGLE MATERIAL RESPONSE 1ST POSITION JACKET CABLE
SURFACE TREATMENTTIN CORE CONDUCTOR ALL CONDUCTORS
SURFACE TREATMENT DOCUMENT AND CLASSIFICATIONASTM B33-63 ASSN STD SINGLE TREATMENT RESPONSE CORE CONDUCTOR ALL CONDUCTORS
ROUND CONDUCTOR SIZE12 AWG ALL CONDUCTORS
STRAND QUANTITY PER CONDUCTOR65 ALL CONDUCTORS
STRAND AWG SIZE PER CONDUCTOR30 ALL CONDUCTORS
CONDUCTOR ARRANGEMENT AND QUANTITY3 SINGLES
VOLTAGE RATING600.0 MAXIMUM ROOT MEAN SQUARE (RMS) OPERATING VOLTAGE ALL CONDUCTORS
CROSS-SECTIONAL SHAPE STYLEROUND
CROSS SECTION OUTSIDE DIAMETER0.502 INCHES NOMINAL
TEMP RATING-55.0 DEG CELSIUS AND
75.0 DEG CELSIUS


Click here to Register for Free 30-day Trial